Can anyone recommend a charger (or type of charger) to use for recharging a 24v lead acid leisure battery bank from a backup generator? Currently we have a cheap charger bought online but it only puts out about 130 watts, which means running it for quite a long time to significantly recharge the batteries and is much less than gets fed to them when the sun shines. TIA

  • perestroika@slrpnk.netM
    link
    fedilink
    arrow-up
    2
    ·
    edit-2
    6 days ago

    Then take one that can take about 80% of the generator power and feed that into the battery bank. Size the charger to the lower of both numbers.

    80% feels like too much.

    My electric car has a 1600 W charging mode. My emergency gasoline generator supplies 2100 W theoretically if the power factor is 1 (totally resistive load). When I connect my charger in 1600 W mode, the generator trips and drops the load, however. It manages to work at 1200 W or below. And this happens despite the charger having a slow ramp-up behaviour (it doesn’t go to full load in a second, but during 5 seconds).

    So based on experience, I would advise to pick a charger that can take 50…60% of the generator’s power.

    For a 24V lead acid battery, look for chargers designed for warehouse equipment (forklifts), wheelchairs, truck batteries and such.

    • nomad@infosec.pub
      link
      fedilink
      arrow-up
      2
      ·
      5 days ago

      Your car has a charge controller and a temperature sensor in the battery pack. A dumb charger with too much capacity could in theory overload the battery and get it too hot.

      • perestroika@slrpnk.netM
        link
        fedilink
        arrow-up
        2
        ·
        edit-2
        5 days ago

        It definitely has. But in my case, I’m not bypassing it - the external part of the charger is communicating to the car using the Type 1 interface and telling “charge at X amps”. (But I know that’s not applicable to DIY situations.)

        …and since the tripping occurs within the ramp-up period or very soon after (e.g. on second 7), I’m fairly certain nothing has managed to overheat yet. I think that some generators have poor steering regulators, mine included.